Functional Safety Play Book

279 members • Free

1 contribution to Functional Safety Play Book
SIL Calculation
Good day everyone, I have few questions on SIL Calculation. I have a PILZ controller in SIF and try to make some calculation by hand. Controller has DI and DO with CPU. 1. If I would like to calculate PFDavg for Controller then I should combine DI, DO and CPU PFD avarage, correct? (No redundancy at DIs and DOs) For ex, PFD input, single + PFD output, single+ PFD CPU = 2,20 x 10^-4 + 1,30 x 10^-5 + 6,20 x 10^-5 (See please certificate) 2. As you see the certificate shows only PFD but not λ DU. Can I calculate my λDU from PFD as referencing the formula below? PFDavg = (λDU * T)/2 . Actually, the certificate does not say what T has been taken into account on PFD calculation as well, but I am going to take it as 1 year. 3. CPU Part: 773103 ( PNOZ m1p ETH) ; Certificate Link: https://www.pilz.com/download/open/PNOZmulti_TUEV-Sued_BM_M6A-020132-0284-R01_R4_4_valid_2030-Jun-24_1002803-BM-34.pdf Thank you!
0
0
1-1 of 1
Khalid Kalbiyev
1
5 points to level up
@khalid-kalbiyev-3329
I&C Engineer | Preventing surprises before they happen!

Active 4d ago
Joined Jul 16, 2026
Charleston, TN